Chapter 1 Overview

Module Operation

As shown in the block diagram below, each input channel of the module
consists of an RTD/resistance connection that accepts excitation current; a
sense connection that detects lead wire resistance; and a return connection.
The signals are multiplexed to an A/D converter that reads the RTD or
resistance value and the lead wire resistance.

From the readings taken by the converter, the module returns an accurate
temperature or resistance to the controller user program through the
microprocessor. The module uses two bidirectional serial ports for
communication, each using an optocoupler for isolation. A third optocoupler
is used to reset the microprocessor if the module detects a loss of
communication.