88

Rockwell Automation Publication 1769-UM005B-EN-P - March 2012

Chapter 5 Diagnostics and Troubleshooting

Module Inhibit Function

Some controllers support the module inhibit function. See your controller
manual for details.

Whenever the 1769-IR6 module is inhibited, the module continues to provide
information about changes at its inputs to the 1769 CompactBus master (for
example, a CompactLogix controller).

Module Specific
Configuration
Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

Invalid input filter selected (channel 0)

X402

010

0 0000 0010

Invalid input filter selected (channel 1)

X403

010

0 0000 0011

Invalid input filter selected (channel 2)

X404

010

0 0000 0100

Invalid input filter selected (channel 3)

X405

010

0 0000 0101

Invalid input filter selected (channel 4)

X406

010

0 0000 0110

Invalid input filter selected (channel 5)

X407

010

0 0000 0111

Invalid input format selected (channel 0)

X408

010

0 0000 1000

Invalid input format selected (channel 1)

X409

010

0 0000 1001

Invalid input format selected (channel 2)

X40A

010

0 0000 1010

Invalid input format selected (channel 3)

X40B

010

0 0000 1011

Invalid input format selected (channel 4)

X40C

010

0 0000 1100

Invalid input format selected (channel 5)

X40D

010

0 0000 1101

Invalid excitation current for input range selected (channel 0)

X40E

010

0 0000 1110

Invalid excitation current for input range selected (channel 1)

X40F

010

0 0000 1111

Invalid excitation current for input range selected (channel 2)

X410

010

0 0001 0000

Invalid excitation current for input range selected (channel 3)

X411

010

0 0001 0001

Invalid excitation current for input range selected (channel 4)

X412

010

0 0001 0010

Invalid excitation current for input range selected (channel 5)

X413

010

0 0001 0011

Invalid calibration enable word