Rockwell Automation 1769-IR6 Compact I/O 1769-IR6 RTD/Resistance Input Module User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 1769-UM005B-EN-P - March 2012

Chapter 4 Module Data, Status, and Channel Configuration

Table 7 - Channel Configuration Bit Definitions

To Select

Make these bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Filter Frequency

10 Hz

1

1

0

60 Hz

0

0

0

50 Hz

0

0

1

250Hz

0

1

1

500 Hz

1

0

0

1 kHz

1

0

1

Excitation
Current

1.0 mA

0

0.5 mA

1

Cyclic Lead
Compensation

Enable

0

Disable

1

Open/Broken Circuit
Response

Upscale

0

0

Downscale

0

1

Last State

1

0

Zero

1

1

Temperature
Units/Mode

(1)

°C

0

°F

1

Input/Sensor Type

100

Ω Platinum 385

0

0

0

0

200

Ω Platinum 385

0

0

0

1

500

Ω Platinum 385

0

0

1

0

1000

Ω Platinum 385

(2)

0

0

1

1

100

Ω Platinum 3916

0

1

0

0

200

Ω Platinum 3916

0

1

0

1

500

Ω Platinum 3916

0

1

1

0

1000

Ω Platinum 3916

(2)

0

1

1

1

10 Copper 426

(3)

1

0

0

0

120 Nickel 618

1

0

0

1

120 Nickel 672

1

0

1

0

604 Nickel-Iron 518

1

0

1

1

150

Ω

1

1

0

0

500

Ω

1

1

0

1

1000

Ω

1

1

1

0

3000

Ω

(2)

1

1

1

1

Advertising