Configuring Channels

After module installation, you must configure operation details, such as RTD
type and temperature units, for each channel. Channel configuration data for
the module is stored in the controller configuration file, which is both readable
and writable.

Configuration Data File

The configuration data file is shown below. Bit definitions are provided in
Channel Configuration on page 51. Detailed definitions of each of the
configuration parameters follows the table.

The default configuration of the table is all zeros, which yields the following.

TIP

Normal channel configuration is done using programming
software. In that case, it is not necessary to know the
meaning of the bit location. However, some systems allow
configuration to be changed by the control program. Refer
to your controller’s documentation for details.

Table 5 - Default Configuration

Parameter

Default Setting

Channel Enable/Disable

Disable

Data Format

Raw/Proportional

Input/Sensor Type

100

Ω Platinum 385

Temperature Units/Mode

°C (not applicable with Raw/Proportional)

Open/Broken Circuit Response

Upscale

Cyclic Lead Compensation

Enable

Excitation Current

1.0 mA

Input FIlter Frequency

60 Hz