Module Data, Status, and Channel Configuration Chapter 4

Effects of Autocalibration
on Accuracy

The module performs autocalibration to correct for drift errors over
temperature. Autocalibration occurs immediately following configuration of a
previously unselected channel, during power cycle of enable channels and
every 5 minutes if so configured. The table below shows module accuracy with
and without calibration.

Table 21 - Module Accuracy

Input Type

(1)

(2)

With Autocalibration

Without Autocalibration

Maximum Error at
25

°C (77 °F)

Maximum Error at
60

°C (140 °F)

Temperature Drift (0…60

°C)

(32…140 °F)

100

Ω Platinum 385

±

0.5

°C (±0.9 °F)

±

0.9

°C (±1.62 °F)

±

0.026

°C/°C (±0.026 °F/°F)

200

Ω Platinum 385

±

0.5

°C (±0.9 °F)

±

0.9

°C (±1.62 °F)

±

0.026

°C/°C (±0.026 °F/°F)

500

Ω Platinum 385

±

0.5

°C (±0.9 °F)

±

0.9

°C (±1.62 °F)

±

0.026

°C/°C (±0.026 °F/°F)

1000

Ω Platinum 385

±

0.5

°C (±0.9 °F)

±

0.9

°C (±1.62 °F)

±

0.026

°C/°C (±0.026 °F/°F)

100

Ω Platinum 3916

±

0.4

°C (±0.72 °F)

±

0.8

°C (±1.44 °F)

±

0.023

°C/°C (±0.023 °F/°F)

200

Ω Platinum 3916

±

0.4

°C (±0.72 °F)

±

0.8

°C (±1.44 °F)

±

0.023

°C/°C (±0.023 °F/°F)

500

Ω Platinum 3916

±

0.4

°C (±0.72 °F)

±

0.8

°C (±1.44 °F)

±

0.023

°C/°C (±0.023 °F/°F)

1000

Ω Platinum 3916

±

0.4

°C (±0.72 °F)

±

0.8

°C (±1.44 °F)

±

0.023

°C/°C (±0.023 °F/°F)

10

Ω Copper 426

±

0.8

°C (±1.44 °F)

±

1.1

°C (±1.98 °F)

±

0.032

°C/°C (±0.032 °F/°F)

120

Ω Nickel 618

±

0.3

°C (±0.54 °F)

±

0.5

°C (±0.9 °F)

±

0.012

°C/°C (±0.012 °F/°F)

120

Ω Nickel 672

±

0.3

°C (±0.54 °F)

±

0.5

°C (±0.9 °F)

±

0.012

°C/°C (±0.012 °F/°F)

604

Ω Nickel-Iron 518

±

0.3

°C (±0.54 °F)

±

0.5

°C (±0.9 °F)

±

0.015

°C/°C (±0.015 °F/°F)

150

Ω

±

0.15

Ω

±

0.25

Ω

±

0.007

Ω/°C (±0.012 Ω/°F)

500

Ω

±

0.5

Ω

±

0.8

Ω

±

0.023

Ω/°C (±0.041 Ω/°F)

1000

Ω

±

1.0

Ω

±

1.5

Ω

±

0.043

Ω/°C (±0.077 Ω/°F)

3000

Ω

±

1.5

Ω

±

2.5

Ω

±

0.07

Ω/°C (±0.130 Ω/°F)

(1) The accuracy values apply to both current sources.
(2) Above ratings apply when a 50/60 Hz filter is used.

Advertising