Module addressing, Appendix a, Appendix a. f – Rockwell Automation 1769-IR6 Compact I/O 1769-IR6 RTD/Resistance Input Module User Manual

Page 91: I:e.6/2, Appendix

Advertising
background image

Rockwell Automation Publication 1769-UM005B-EN-P - March 2012

91

Appendix

A

Module Addressing and Programming with
MicroLogix 1500 and RSLogix 500

Module Addressing

The module uses eight input words for data and status bits (input image), and
seven configuration words.

For example, to obtain the general status of channel 2 of the module located in
slot e, use address I:e.6/2.

Channel 0 Data Word

Word 0
Word 1
Word 2
Word 3

Word 4

Word 5

Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word

General/Open-Circuit Status Bits

Over-/Under-range Bits

Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word

I:e.0
I:e.1

I:e.2

I:e.3
I:e.4
I:e.5

Word 0
Word 1
Word 2
Word 3

Address

Input Image

8 words

Configuration

File

7 words

slot e

slot e

Input Image

File

Configuration

File

Memory Map

Bit 15

Bit 0

Refer to your
controller
manual for the
addresses.

Channel 3 Data Word
Channel 3 Data Word

Word6

Word 7

I:e.6
I:e.7

Channel 4 Configuration Word
Channel 5 Configuration Word

Word 4
Word 5

Module Configuration Word

Word 6

I:e.6/2

Input File Type

Slot

Word

Bit

Bit Delimiter

Word Delimiter

Element Delimiter