Enabling or disabling a channel (bit 15) – Rockwell Automation 1769-IR6 Compact I/O 1769-IR6 RTD/Resistance Input Module User Manual

Page 53

Advertising
background image

Rockwell Automation Publication 1769-UM005B-EN-P - March 2012

53

Module Data, Status, and Channel Configuration Chapter 4

Enabling or Disabling a Channel (Bit 15)

Bit 15 enables or disables each of the six channels individually. The module
only scans those channels that are enabled. Enabling a channel forces it to be
recalibrated before it measures input data. Turning a channel off results in the
channel data being set to zero.

Data Format

Raw/Proportional

0

0

0

Engineering Units

0

0

1

Engr. Units X 10

1

0

0

Scaled-for-PID

0

1

0

Percent Range

0

1

1

Enable/Disable
Channel

Enable

1

Disable

0

(1) Ignored for a resistance device input.
(2) Valid only with the 0.5 mA excitation current.
(3) Valid only with the 1.0 mA excitation current.

Table 7 - Channel Configuration Bit Definitions

To Select

Make these bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

TIP

When a channel is not enabled, the A/D converter
provides no input to the controller. This speeds up the
system response of the active channels.

The configuration default is to disable each input channel
to maximize module performance.