Enabling or Disabling a Channel (Bit 15)
Bit 15 enables or disables each of the six channels individually. The module
only scans those channels that are enabled. Enabling a channel forces it to be
recalibrated before it measures input data. Turning a channel off results in the
channel data being set to zero.
Data Format
Raw/Proportional
0
0
0
Engineering Units
0
0
1
Engr. Units X 10
1
0
0
Scaled-for-PID
0
1
0
Percent Range
0
1
1
Enable/Disable
Channel
Enable
1
Disable
0
(1) Ignored for a resistance device input.
(2) Valid only with the 0.5 mA excitation current.
(3) Valid only with the 1.0 mA excitation current.
Table 7 - Channel Configuration Bit Definitions
To Select
Make these bit settings
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
TIP
When a channel is not enabled, the A/D converter
provides no input to the controller. This speeds up the
system response of the active channels.
The configuration default is to disable each input channel
to maximize module performance.