Configuring the 1769-IR6 RTD Module with the Generic Profile Appendix B
For demonstration purposes, a Generic Profile has been created for 1769- IR6
module. The Controller Tags screen looks like the following:
Tag addresses are automatically created for configured I/O modules. All local
I/O addresses are preceded by the word Local. These addresses have the
following format:
·
Input Data: Local:s:I
·
Configuration Data: Local:s:C
Where s is the slot number assigned the I/O modules in the Generic
Profiles.
In order to configure an I/O module, you must open up the configuration tag
for that module by clicking on the plus sign to the left of its configuration tag
in the Controller Tag data base.