2-2 Installation and Wiring

 Industrial Automation, Wiring and Grounding Guidelines for Noise

Immunity, publication 1770-4.1

 Automation Systems Catalog, publication B113

Power Requirements

The modules receive power through the bus interface from the +5V dc/+24V
dc system power supply.

Table 2.1 Maximum Current Draw

General Considerations

The Compact I/O system is suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution degree
2

(1)

) and to circuits not exceeding Over Voltage Category II

(2)

(IEC

60664-1).

(3)

Module

5V dc

24V dc

1769-IF4I (Series A)

145 mA

125 mA

1769-OF4CI (Series A)

145 mA

140 mA

1769-OF4VI (Series A)

145 mA

75 mA

(1)

Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.

(2)

Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.

(3)

Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.