4-12 Module Data, Status, and Channel Configuration for the Output Modules

Ramping only takes place, if configured, when the output is being commanded
to go to a fault state. Ramping is not done in normal run operation. The ramp
rate values are entered in the Configuration Data file and are accepted as valid
only if:

 the number of counts entered for a channel’s ramp rate is greater than or

equal to a minimum of 1% of the total number of full scale counts for
the channel’s selected data format.

See Ramping Types on page 4-11 and 1769-OF4CI Output
Range/Types and Output Data Formats on page 4-11 for minim
um
values.

or

 the number of counts entered for a channel’s ramp rate may be equal to

0 if ramping is not enabled for the channel.

Table 4.10 1769-OF4VI Output Range/Types and Output Data Formats

Output Data

Format Output

Range/Type

Total Counts in

Full Scale

Number of Counts

for Every 1% of

Ramp Rate

Real Units/Second

for Every 1% of

Ramp Rate

Proportional Counts
-10…+10V

65534

655

0.2V/s

0…5V

0.05V/s

0…10V

0.1V/s

1…5V

0.04V/s

Engineering Units
-10…+10V

21000

210

0.2V/s

0…5V

5750

58

0.05V/s

0…10V

11000

110

0.1V/s

1…5V

4750

48

0.04V/s

Scaled for PID
-10…+10V

16383

164

0.2V/s

0…5V

0.05V/s

0…10V

0.1V/s

1…5V

0.04V/s

Percent of Full Scale
-10…+10V

10000

100

0.2V/s

0…5V

0.05V/s

0…10V

0.1V/s

1…5V

0.04V/s