Publication 1769-UM014B-EN-P - May 2010

B-4 Module Addressing and Configuration with MicroLogix 1500

Configure Analog I/O

Modules in a MicroLogix

1500 System

This example takes you through configuring your 1769 analog input and
output modules with RSLogix 500 programming software. This application
example assumes your input and output modules are installed as expansion
I/O in a MicroLogix 1500 system, and that RSLinx software is properly
configured and a communications link has been established between the
MicroLogix controller and RSLogix 500 software.

If you have RSLogix 500, version 6 or earlier, follow this procedure to
configure your module.

1. From the list, choose Other:Requires I/O Card Type ID.

2. Enter the appropriate values as listed below.

3. Choose OK.

4. From the Generic Extra Data Config tab, enter your configuration data.

Vendor ID = 1
Product Type = 109
Product Code = 66
Series/Major Rev/Minor Rev = A
Input Words = 108
Input Bits = 0
Output Words = 108
Output Bits = 0
Extra Data Length = 31