Publication 1769-UM014B-EN-P - May 2010

B-2 Module Addressing and Configuration with MicroLogix 1500

Input Module’s Input Image

The input modules’ input image file represents data words and status bits.
Input words 0 to 3 hold the input data that represents the value of the analog
inputs for channels 0 to 3. These data words are valid only when the channel is
enabled and there are no errors. Input words 4 and 5 hold the status bits. To
receive valid status information, the channel must be enabled.

For example, to obtain the general status of channel 2 of the analog module
located in slot 3, use address I:3.4/2.

TIP

The end cap does not use a slot address.

I:3.4/2

Input File Type

Slot

Word

Bit

Bit Delimiter

Word Delimiter

Element Delimiter