1769-of4ci and -of4vi enable/disable channel, 1769-of4ci and -of4vi enable/disable channel -9 – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 61

Advertising
background image

Publication 1769-UM014B-EN-P - May 2010

Module Data, Status, and Channel Configuration for the Output Modules 4-9

1769-OF4CI and -OF4VI Enable/Disable Channel

This configuration selection (bit 15 of Configuration Word 0) allows each
channel to be individually enabled.

Table 4.7 1769-OF4CI and -OF4VI Output Channel Configuration Word 1

Define

Indicate

Bit Settings

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1769-OF4CI

Output

Range

Select

0…20 mA dc

0 0 0

4…20 mA dc

0 0 1

Output

Data

Select

Raw/Proportion

al Counts

0 0 0

Engineering

Units

0 0 1

Scaled for PID

0 1 0

Percent Range

0 1 1

1769-OF4VI

Output

Range

Select

-10…+10V dc

0 0 0

0…5V dc

0 0 1

0…10V dc

0 1 0

1…5V dc

0 1 1

Output

Data

Select

Raw/Proportion

al Counts

0 0 0

Engineering

Units

0 0 1

Scaled for PID

0 1 0

Percent Range

0 1 1

TIP

A channel that is not enabled has zero voltage or current at
its terminal.