1769-of4vi output specifications – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 89

Advertising
background image

Publication 1769-UM014B-EN-P - May 2010

Specifications A-7

1769-OF4VI Output

Specifications

Table A.4 1769-OF4VI Specifications

Specification

1769-OF4VI

Analog Normal Operating
Ranges

(1)

(1)

The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will

continue to convert the analog output up to the maximum full scale range. The flag automatically resets when within the

normal operating range unless configured to latch.

± 10V dc, 0…10V dc, 0…5V dc, 1…5V dc

Full Scale Analog Ranges

(1)

± 10.5V dc, -0.5…10.5V dc, -0.5…5.25V dc,

0.5…5.25V dc

Number of Outputs

4 isolated differential

Bus Current Draw, Max

145 mA at 5V dc

75 mA at 24V dc

Heat Dissipation

2.0 total W (All points - 10V dc into 2 k - worst case

calculated.)

Digital Resolution Across Full

Range

16 bits plus sign (bipolar)

±10V dc: 15.89 bits, 330 µV/bit

0…+5V dc: 13.89 bits, 330 µV/bit

0…+10V dc: 14.89 bits, 330 µV/bit

+1…+5V dc: 13.57 bits, 330 µV/bit

Conversion Rate (all channels),

Max

120 ms

Step Response to 63%

(2)

(2)

Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until

the device is at 63% of full range.

<2.9 ms

Current Load Output, Max

5 mA

Load Range Output

> 2 kat 10V dc

Capacitive Load, Max

1 µF

Field Calibration

None required

Overall Accuracy

(3)

(3)

Includes offset, gain, drift, non-linearity and repeatability error terms.

±0.5% full scale at 25 °C

Advertising