3-6 Module Data, Status, and Channel Configuration for the Input Module

1769-IF4I Configuration

Data File

The configuration file lets you determine how each individual input channel
will operate. Parameters such as the input type and data format are set up using
this file. This data file is writable and readable. The default value of the
configuration data table is all zeros.

The configuration file is typically modified using the programming software
configuration screen.

For information on configuring the module using MicroLogix 1500 and
RSLogix 500 software, see Appendix B; for CompactLogix and RSLogix 5000
software, see Appendix C; for 1769-ADN DeviceNet adapter and RSNetWorx
software, see Appendix D.

The configuration file can also be modified through the control program, if
supported by the controller. The structure and bit settings are shown in
Channel Configuration on page 3-7.

Table 3.3 1769-IF8 Configuration Data Table

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Real Time Sample Value

1

ETS

Reserved

2

EC

Reserved

EA

AL

EI

(1)

Reserved

Input Filter Sel Chl0

3

Reserved

Inpt Dta Fm Chl0

Reserved

Inpt Tp/RngeSel Chl0

4

S

Process Alarm High Data Value Channel 0

5

S

Process Alarm Low Data Value Channel 0

6

S

Alarm Dead Band Value Channel 0

7

Reserved

8

EC

Reserved

EA

AL

EI

(1)

Reserved

Inpt Filter Sel Chl1

9

Reserved

Inpt Dta Fm Chl1

Reserved

Inpt Tp/RngeSel Chl1

10

S

Process Alarm High Data Value Channel 1

11

S

Process Alarm Low Data Value Channel 1

12

S

Alarm Dead Band Value Channel 1

13

Reserved

14

EC

Reserved

EA

AL

EI

(1)

Reserved

Input Filter Sel Chl2

15

Reserved

Inpt Dta Fm Chl2

Reserved

Inpt Tp/RngeSel Chl2

16

S

Process Alarm High Data Value Channel 2

17

S

Process Alarm Low Data Value Channel 2

18

S

Alarm Dead Band Value Channel 2

19

Reserved

20

EC

Reserved

EA

AL

EI

(1)

Reserved

Input Filter Sel Chl3

21

Reserved

Inpt Dta Fm Chl3

Reserved

Inpt Tp/RngeSel Chl3

22

S

Process Alarm High Data Value Channel 3

23

S

Process Alarm Low Data Value Channel 3

24

S

Alarm Dead Band Value Channel 3

25

Reserved

(1)

CompactLogix L43 controllers will be able to support these interrupts.