Remove the finger-safe terminal block, Wire the finger-safe terminal block – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 32

Advertising
background image

Publication 1769-UM014B-EN-P - May 2010

2-16 Installation and Wiring

Remove the Finger-safe Terminal Block

When wiring field devices to the module, it is not necessary to remove the
terminal block. If you remove the terminal block, use the write-on label on the
side of the terminal block to identify the module slot location and type. RTB
position can be indicated by circling either the R for right side or L for left
side.

Figure 2.7 Finger-safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining screws.
The terminal block will back away from the module as you remove the screws.
When replacing the terminal block, torque the retaining screws to 0.46 Nm
(4.1 lb-in).

Wire the Finger-safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1. Loosen the terminal screws to be wired.

2. Begin wiring at the bottom of the terminal block and move up.

3. Route the wire under the terminal pressure plate. You can use the bare

wire or a spade lug. The terminals accept a 6.35 mm (0.25 in.) spade lug.

TIP

The terminal screws are non-captive. Therefore, it is
possible to use a ring lug (maximum 1/4 in. o.d. with a
0.139 in. minimum i.d. (M3.5)) with the module.

SLOT # _____

MODULE TYPE ______

Advertising