Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 90

Advertising
background image

Publication 1769-UM014B-EN-P - May 2010

A-8 Specifications

Table A.4 1769-OF4VI Specifications

Specification

1769-OF4VI

Accuracy Drift with

Temperature

±0.0086% FS per °C

Output Ripple

(1)

Range 0…50 kHz

(referred to output range)

±0.05%

Non-linearity (in percent full

scale)

±0.05%

Repeatability

(2)

(in percent full scale)

±0.05%

Output Error Over Full

Temperature Range

0…60 °C (+32…+140 °F)

±0.8%

Output Impedance

<1 

Open and Short-circuit

Protection

Yes

Maximum Short-circuit Current 30 mA
Output Overvoltage Protection Yes
Output Response at System

Power Up and Power Down

Power up: +1.2V dc spike for less than 0.4 ms

Power down: 1.2V dc spike for less than 21 ms

Rated Working Voltage

(3)

30V ac/30V dc

Output Group to Bus Isolation

500V ac or 710V dc for 1 minute (qualification test)

30V ac/30V dc working voltage

Module OK LED

On: module has power, has passed internal diagnostics,

and is communicating over the bus.

Off: Any of the above is not true.

Channel Diagnostics

Over- or under-range by bit reporting

System Power Supply Distance

Rating

The module may not be more than 8 modules away from

the system power supply.

Recommended Cable

Belden 8761 (shielded)

Vendor I.D. Code

1

Product Type Code

10

Product Code

42

Input Words

6

Output Words

5

Configuration Words

32

(1)

Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.

(2)

Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it

consecutively, under the same conditions and in the same direction.

(3)

Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input

signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above ground).