Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 79

Advertising
background image

Publication 1769-UM014B-EN-P - May 2010

Module Diagnostics and Troubleshooting 5-7

1769-IF4I Specific

Configuration

Error

X400

010

0 0000 0000

General configuration error; no additional information

X403

010

0 0000 0011

Invalid real time sample rate value

X404

010

0 0000 0100

Invalid input filter selected (channel 0)

X405

010

0 0000 0101

Invalid input filter selected (channel 1)

X406

010

0 0000 0110

Invalid input filter selected (channel 2)

X407

010

0 0000 0111

Invalid input filter selected (channel 3)

X408

010

0 0000 1000

Invalid input range selected (channel 0)

X409

010

0 0000 1001

Invalid input range selected (channel 1)

X40A

010

0 0000 1010

Invalid input range selected (channel 2)

X40B

010

0 0000 1011

Invalid input range selected (channel 3)

X40C

010

0 0000 1100

Invalid input format selected (channel 0)

X40D

010

0 0000 1101

Invalid input format selected (channel 1)

X40E

010

0 0000 1110

Invalid input format selected (channel 2)

X40F

010

0 0000 1111

Invalid input format selected (channel 3)

X410

010

0 0001 0000

Invalid low alarm data value (channel 0)

X411

010

0 0001 0001

Invalid low alarm data value (channel 1)

X412

010

0 0001 0010

Invalid low alarm data value (channel 2)

X413

010

0 0001 0011

Invalid low alarm data value (channel 3)

X414

010

0 0001 0100

Invalid high alarm data value (channel 0)

X415

010

0 0001 0101

Invalid high alarm data value (channel 1)

X416

010

0 0001 0110

Invalid high alarm data value (channel 2)

X417

010

0 0001 0111

Invalid high alarm data value (channel 3)

X418

010

0 0001 1000

Invalid alarm deadband value (channel 0)

X419

010

0 0001 1001

Invalid alarm deadband value (channel 1)

X41A

010

0 0001 1010

Invalid alarm deadband value (channel 2)

X41B

010

0 0001 1011

Invalid alarm deadband value (channel 3)

X41C

010

0 0001 1100

Alarm not enabled (channel 0)

X41D

010

0 0001 1101

Alarm not enabled (channel 1)

X41E

010

0 0001 1110

Alarm not enabled (channel 2)

X41F

010

0 0001 1111

Alarm not enabled (channel 3)

(1)

X represents the Don’t Care digit.

Table 5.4 1769-IF4I Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

Advertising