2-10 Installation and Wiring

System Wiring Guidelines

Consider the following when wiring your system.

General Guidelines

 Channels are isolated from each other.
 Do not use the analog module’s NC terminals as connection points.
 To ensure optimum accuracy, limit overall cable impedance by keeping

your cable as short as possible. Locate the I/O system as close to your
sensors or actuators as your application will permit.

 Use Belden 8761, or equivalent, shielded wire.
 Keep shield connection to ground as short as possible.
 Under normal conditions, the drain wire and shield junction must be

connected to earth ground via a panel or DIN rail mounting screw at
the analog I/O module end.

(1)

(1)

In environments where high-frequency noise may be present, it may be necessary to directly ground cable
shields to earth at the module end and via a 0.1µF capacitor at the sensor end.