5-8 Module Diagnostics and Troubleshooting

Table 5.5 1769-OF4CI and -OF4VI Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common

Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power cycle reset state

X216

001

0 0001 0110

Microprocessor watchdog error

X220

001

0 0010 0000

Firmware corrupt (checksum failure)

X221

001

0 0010 0001

Firmware checksum error in NVRAM (calibration data checksum

failure)

Hardware-

Specific Error

X300

001

1 0000 0000

General hardware error (ASIC)

1769-OF4CI and

-OF4VI Specific

Configuration

Error

X401

010

0 0000 0001

Invalid input range selected (channel 0)

X402

010

0 0000 0010

Invalid input range selected (channel 1)

X403

010

0 0000 0011

Invalid input range selected (channel 2)

X404

010

0 0000 0100

Invalid input range selected (channel 3)

X409

010

0 0000 1001

Invalid data format selected (channel 0)

X40A

010

0 0000 1010

Invalid data format selected (channel 1)

X40B

010

0 0000 1011

Invalid data format selected (channel 2)

X40C

010

0 0000 1100

Invalid data format selected (channel 3)

X411

010

0 0001 0001

Invalid fault value (channel 0)

X412

010

0 0001 0010

Invalid fault value (channel 1)

X413

010

0 0001 0011

Invalid fault value (channel 2)

X414

010

0 0001 0100

Invalid fault value (channel 3)

X419

010

0 0001 1001

Invalid idle value (channel 0)

X41A

010

0 0001 1010

Invalid idle value (channel 1)

X41B

010

0 0001 1011

Invalid idle value (channel 2)

X41C

010

0 0001 1100

Invalid idle value (channel 3)

X421

010

0 0010 0001

Invalid clamps (channel 0)

X422

010

0 0010 0010

Invalid clamps (channel 1)

X423

010

0 0010 0011

Invalid clamps (channel 2)

X424

010

0 0010 0100

Invalid clamps (channel 3)

X429

010

0 0010 1001

Invalid ramp rate (channel 0)

X42A

010

0 0010 1010

Invalid ramp rate (channel 1)

X42B

010

0 0010 1011

Invalid ramp rate (channel 2)

X42C

010

0 0010 1100

Invalid ramp rate (channel 3)