1769-of4ci and -of4vi channel configuration, 1769-of4ci and -of4vi channel configuration -8 – Rockwell Automation 1769-OF4VI Compact I/O Isolated Analog Modules User Manual

Page 60

Advertising
background image

Publication 1769-UM014B-EN-P - May 2010

4-8 Module Data, Status, and Channel Configuration for the Output Modules

1769-OF4CI and -OF4VI Channel Configuration

The first two words of each eight word group in the configuration file allow
you to change the parameters of each channel independently. For example,
words 8 and 9 correspond to channel 1 while words 24 and 25 correspond to
channel 3.

Table 4.6 1769-OF4CI and -OF4VI Channel Configuration Word 0

(1)

Define

Indicate

Bit Settings

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Program (Idle) to

Fault Enable

Program (Idle)

Mode Data
Applied

(2)

0

Fault Mode
Data Applied

(2)

1

Hold for

Initialization

Disabled

0

Enabled

1

Program (Idle)

Mode

Hold Last
State

(2)

0

User-Defined
Value

(2)

1

Fault Mode

Hold Last
State

(2)

0

User-Defined
Fault Value

(2)

1

Enable Ramping

Disabled

0

Enabled

(2)

1

Enable Clamp/

Alarm Latching

Disabled

0

Enabled

1

Enable High

Clamp/ Alarm

Interrupt

Disabled

0

Enabled

(2)

1

Enable Low

Clamp/ Alarm

Interrupt

Disabled

0

Enabled

(2)

1

Enable Channel

Disabled

0

Enabled

1

(1)

Refer to the 1769-OF4CI and -OF4VI Output Channel Configuration Word 1 table.

(2)

Hold Last State and User Defined Fault functionality is only supported when the analog module is used in a DeviceNet
application via the 1769-ADN adapter No local configuration, that is, a MicroLogix or CompactLogix system, supports this
functionality. Refer to your controller manual for details.