Publication 1769-UM014B-EN-P - May 2010

Module Data, Status, and Channel Configuration for the Input Module 3-7

Channel Configuration

Each channel’s configuration words consist of bit fields, the settings of which
determine how the channel operates. See the table below and the descriptions
that follow for valid configuration settings and their meanings. The default bit
status of the configuration file is all zeros.

Table 3.4 Bit Definitions for Channel Configuration Words

Define

To Select

Make these bit settings
15 14 13 12 11 10 9 8 7…4 3 2 1 0

Input Filter

Selection

60 Hz

0 0 0 0

50 Hz

0 0 0 1

28.5 Hz

0 0 1 0

300 Hz

0 0 1 1

360 Hz

0 1 0 0

Enable

Interrupt

Enable

(1)

(1)

CompactLogix L43 controllers will be able to support these interrupts.

1

Disable

0

Enable

Process

Alarm

Latch

Enable

1

Disable

0

Enable

Process

Alarms

Enable

1

Disable

0

Enable

Channel

Enable

1

Disable

0

Table 3.5 Bit Definitions for Input Range and Input Data

Define Indicate this

These bit settings
15…11 10 9

8

7…4

3 2 1 0

Input

Range

Select

-10…+10V dc

0 0 0 0

0…5V dc

0 0 0 1

0…10V dc

0 0 1 0

4…20 mA

0 0 1 1

1…5V dc

0 1 0 0

0…20 mA

0 1 0 1

Input

Data

Format

Select

Raw/Proportional

Counts

0

0

0

Engineering Units

0

0

1

Scaled for PID

0

1

0

Percent Range

0

1

1