Module Diagnostics and Troubleshooting 5-5

Module Error Field

The purpose of the module error field is to classify module errors into three
distinct groups, as described in the table below. The type of error determines
what kind of information exists in the extended error information field. These
types of module errors are typically reported in the controller’s I/O status file.
Refer to your controller manual for details.

Extended Error Information Field

Check the extended error information field when a non-zero value is present
in the module error field. Depending upon the value in the module error field,
the extended error information field can contain error codes that are
module-specific or common to all 1769 analog modules.

Hardware Errors

General or module-specific hardware errors are indicated by module error
code 2.

See 1769-IF4I Extended Error Codes on page 5-6 and 1769-OF4CI and
-OF4VI Extended Error Codes on page 5-8.

Table 5.3 Module Error Types

Error

Type

Module Error

Field Value

Bits 11…09

(Bin)

Description

No Errors

000

No error is present. The extended error field holds

no additional information.

Hardware

Errors

001

General and specific hardware error codes are

specified in the extended error information field.

Configurat

ion Errors

010

Module-specific error codes are indicated in the

extended error field. These error codes correspond

to options that you can change directly. For

example, the input range or input filter selection.

TIP

If no errors are present in the module error field, the
extended error information field will be set to zero.