Online Operations, Quick Edit

4–11

2.

Monitor input data changes resulting from input device operation.

Press pushbutton 0. Note that the status bit goes from 0 to 1, as the instruction
goes from false to true. Now turn selector switch 6 to the on position. Note that
status bit I:2/2 goes from 0 to 1, as the instruction goes from false to true.

3.

Access the output data file.

The output data file precedes the input data file in the data table. Press

CONFIG

OFFLINE

CONFIG

PREV

FILE

F8

. The output data file appears. Since we didn’t specify a particular

bit address, the cursor is located on the status bit having the lowest address,
O:3/0. This is also the status bit for pilot light 0 in our program. This is shown
below.

address 15 data 0 address 15 data 0
O:3 0000 0000

Press a key or enter value

O:3/0 =

REM RUN

no forces

binary data decimal addr

PROC Addr 1

F7

F5

NEXT

FILE

SPECIFY

ADDRESS

F8

PREV

FIILE

F1

CHANGE

RADIX

F6

FORCE

MONITOR

4.

Monitor output data changes resulting from input device operation.

Press pushbutton 0 with selector switch 6 in the on position. Note that status bit
O:3/0 goes from 0 to 1, as the output instruction of our program goes from false
to true.

Continue to press pushbutton 0, as you turn selector switch 6 to the off position.
Note that bit O:3/0 goes from 1 to 0. This is because there is no longer a path of
true input instructions in the rung, causing the output instruction to go false.