Table B.C
Processor Error Codes

Error Code

Cause

Corrective Action

0001

RAM program is corrupt

due to noise, lightning,

improper grounding or

loss of capacitor or batĆ

tery backĆup.

Check wiring, layout, grounding. If using a 4K

CPU, verify that a battery is installed to retain

RAM memory when power is removed. See

CPU FAULTĆFlashing under system LED status.

Restore the program using APS or an HHT.

0012

RAM program is corrupt

or RAM itself is bad due

to noise, lightning, imĆ

proper grounding, or

loss of capacitor or batĆ

tery backĆup.

Check wiring, layout, grounding. If using a 4K

CPU, verify that a battery is installed to retain

RAM memory when power is removed. See

CPU FAULTĆFlashing under system LED status.

Restore the program using APS or an HHT.

XX50, XX51, XX52

XX53, XX54, XX55

(xx = slot #)

I/O module configuraĆ

tion/conflict or runtime

problem.

Verify that processor configuration matches

your hardware by pressing F3 Offline Prg/Doc";

F1 Procssr Functns"; F1 Change Procssr"; F5

Configr I/O"; See CPU FAULTĆFlashing under

the system LED status.

XX56

(xx = slot #)

Chassis configuration

error.

Verify that chassis configuration in your program

matches your hardware by pressing F3 Offline

Prg/Doc"; F1 Procssr Functns"; F1 Change

Procssr"; F5 Configr I/O". If multiple chassis

system, verify proper installation of chassis inĆ

terconnect cable. See CPU FAULT Ć Flashing

under system LED status.