Rockwell Automation 9323-PA1E QUICK START GUIDE APS 6.0 User Manual

Page 70

Advertising
background image

Troubleshooting

B–3

Table B.A
APS Error Messages (continued)

Error Message

Possible Causes

Corrective Action

I/O Address Not

Configured

Processor/system

configuration does not

match entered

addresses

Verify correct address format (I:slot/terminal

or O:slot/terminal); verify system configuration

by pressing F3 Offline Prg/Doc"; F1 Procssr

Functns"; F1 Change Procssr"; F5 Configr

I/O".

No Matching Disk File

Found

Processor program

does not exist on hard

disk

To read the processor program (upload),

press F8 Yes"; otherwise press F10 No" to

continue with other online activities.

No Memory Left or Not

Enough Memory to

Load Communication

Driver

PC does not have

enough free RAM

memory to continue

Verify your PC has >250K of free RAM to

execute APS. (>369K free RAM is required if

you are running the INTERCHANGE

software). Exit APS and type CHKDSK" at

DOS prompt. The last line should read

>250K bytes free" (or >369K). If not, disable

TSR, drivers, menus, shells, etc. loaded in

AUTOEXEC.BAT or CONFIG.SYS that may

be running in background. ReĆboot PC.

Incompatible

Processor Type

The processor

configuration of the

program you are

restoring does not

match your hardware

Verify that processor configuration of your

program matches your hardware by pressing

F3 Offline Prg/Doc"; F1 Procssr Functns; F1

Change Procssr".