Chapter 10, T5 and v5-code parallel configurations, T5-code parallel configuration – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 105: V5-code parallel configuration, Chapter
Publication 2364P-5.01 December 1999
Chapter
10
T5 and V5-Code Parallel Configurations
T5-Code Parallel Configuration
The T5-code parallel configuration is a common DC bus front-end
unit consisting of an F-code NRU in parallel with two M-code RGUs.
Figure 10.1
T5-Code Parallel Configuration–Information
V5-Code Parallel Configuration
The V5-code parallel configuration is a common DC bus front-end
unit consisting of an G-code NRU in parallel with two M-code RGUs.
Figure 10.2
V5-Code Parallel Configuration–Information
Note: Information for the F-code NRU and G-code NRU can be
found in publication 2364E-5.01. Information for the M-code
RGU can be found in publication 2364F-5.01.
380
2649
1359
460
2650
1677
575
2637
2083
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
M-code
RGU
F-code
NRU
T5-code Parallel Configuration
T5-code Ratings
(Master)
M-code
RGU
(Slave)
380
3000
1539
460
3000
1863
575
3000
2329
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
V5-code Parallel Configuration
V5-code Ratings
M-code
RGU
G-code
NRU
(Master)
M-code
RGU
(Slave)