Chapter 11, T6 and v6-code parallel configurations, T6-code parallel configuration – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 119: V6-code parallel configuration, Chapter

Publication 2364P-5.01 December 1999
Chapter
11
T6 and V6-Code Parallel Configurations
T6-Code Parallel Configuration
The T6-code parallel configuration is a common DC bus front-end
unit consisting of an F-code NRU in parallel with two N-code RGUs.
Figure 11.1
T6-Code Parallel Configuration–Information
V6-Code Parallel Configuration
The V6-code parallel configuration is a common DC bus front-end
unit consisting of a G-code NRU in parallel with two N-code RGUs.
Figure 11.2
V6-Code Parallel Configuration–Information
Note: Information for the F-code NRU and G-code NRU can be
found in publication 2364E-5.01. Information for the N-code
RGU can be found in publication 2364F-5.01.
380
2699
1385
460
2700
1677
575
2683
2083
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
T6-code Parallel Configuration
T5-code Ratings
N-code
RGU
F-code
NRU
(Master)
N-code
RGU
(Slave)
380
3000
1539
460
3000
1863
575
3000
2329
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
V6-code Parallel Configuration
V6-code Ratings
N-code
RGU
G-code
NRU
(Master)
N-code
RGU
(Slave)