Chapter 2, R1 and s1-code parallel configurations, R1-code parallel configuration – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual

Page 25: S1-code parallel configuration, Chapter

Advertising
background image

Publication 2364P-5.01 December 1999

Chapter

2

R1 and S1-Code Parallel Configurations

R1-Code Parallel Configuration

The R1-code parallel configuration is a common DC bus front-end
unit consisting of an D-code NRU in parallel with a K-code RGU.

Figure 2.1
R1-Code Parallel Configuration–Information

S1-Code Parallel Configuration

The S1-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with a K-code RGU.

Figure 2.2
S1-Code Parallel Configuration–Information

Note: Information for the D-code NRU and E-code NRU can be
found in publication 2364E-5.01. Information for the K-code
RGU can be found in publication 2364F-5.01.

380

1520

780

460

1520

944

575

1520

1180

Input Voltage

(V AC)

DC Bus Current

(A DC)

Rated DC Bus

kW

R1-code Parallel Configuration

R1-code Ratings

K-code
RGU

D-code

NRU

380

2020

1036

460

2020

1254

575

2020

1568

Input Voltage

(V AC)

DC Bus Current

(A DC)

Rated DC Bus

kW

S1-code Parallel Configuration

S1-code Ratings

K-code
RGU

E-code

NRU