Input Wiring

Select input wiring which is suitable for the input current and
application environment of the parallel configuration, in accordance
with all applicable codes.

Table 15.A: AC Input Currents

Complete all additional power wiring in the system. If any of the
inverters or external components will be using separate control
power, connect it at this time according to the instructions given in
the respective device manuals.

Configuration

Rated Line Current (A AC)

Code

380 V AC

460V AC

575V AC

R1

1245

1245

1244

R2

1260

1260

1255

R3

1295

1295

1286

R4

1318

1318

1306

S1

1654

1653

1653

S2

1669

1668

1664

S3

1704

1703

1695

S4

1727

1726

1715

T1

2065

2064

2063

T2

2080

2079

2074

T3

2115

2114

2105

T4

2138

2137

2125

T5

2183

2182

2165

T6

2228

2227

2205

V1

2455

2454

2453

V2

2455

2454

2453

V3

2455

2454

2453

V4

2455

2454

2453

V5

2455

2454

2453

V6

2455

2454

2453

W1

1356

1356

1204

W2

1812

1812

1604

W3

2718

2718

2406