Publication 2364P-5.01 December 1999

16-4

Setting Up the Parallel Configuration

Programming the RGU

Using a HIM, GPT, or other programming device, enter the linear
parameter list. The startup procedure below will guide you through
several parameters that need to be configured before operating the
parallel configuration. Program each RGU in the configuration.

Frame Catalog Number [P4]
Enter the frame catalog number of each RGU (this
should correspond to the catalog number shown on
the data name plate of the RGU, located below the
main control board.

RGU Control Mode [P5]
Set this parameter to the appropriate setting:

Master Mode (0) Use this setting if this is a master unit in a lineup of multiple RGUs.
Slave Mode (1)

Use this setting if this is a slave unit in a lineup of multiple RGUs.

Standalone (2)

Use this setting if there are no other RGUs in the lineup (default).

Remote/Local Selector [P8]
Set this parameter to the desired setting (Local Only is default):

Local Only (0)

Use this setting for automatic enabling at startup (HIM/GPT not used for

enable).

Remote+Local (1) Use this setting for manually enabling the RGU via a HIM or GPT.

AC Line Reactor Inductance [P12]
Determine the total line inductance. This is a sum of the RGU line inductance and the transformer
leakage inductance.

P12 = Line Inductance of single RGU + (Transformer Leakage Inductance x #RGUs)

The RGU line inductance values are given below.

For transformer leakage inductance, use the following formulas.

Example
A parallel configuration (catalog number 2364PA-T5B)
is supplied with a transformer which has the example
nameplate shown.

In Appendix B, we find that the catalog number
(2364PA-T5B) indicates the has two 460V AC M-code RGUs.

The line reactors for these units are rated at 137 uH as indicated in the chart above.

To determine the transformer leakage inductance, we can use the 60Hz formula with the
information from the data nameplate.

Add the total line reactor inductance of a single RGU to the transformer leakage inductance times
the number of RGUs to determine the value for P12.

P12 = 137uH + (28uH x 2) = 193uH

AC INPUT

DC OUTPUT

MADE IN U.S.A.

CAT

2364FA-MNB

SER B

Refer to user manual for
installation instructions

CONSTANT TORQUE

Drive Systems

541

460

678

3

50/60

524

683

749

-

DC

VOLTS

A

Hz

KVA

PH

Catalog Number

!

ATTENTION: Changing P4 will reinitialize
all parameters in the RGU and will configure
several key parameters to the catalog number
selected.

2364F- MNB

RGU Cat al og #

St andal one

RGU Cont r ol

Mode

Remot e+Local

Rem/ Loc Sel ect or

Factory
Default

510 (380/460V)
832 (575V)

K-code RGUs

Factory
Default

317 (380/460V)
404 (575V)

L-code RGUs

Factory
Default

137 (380/460V)
191 (575V)

M-code RGUs

Factory
Default

102 (380/460V)
144 (575V)

N-code RGUs

(at 60Hz)

(at 50Hz)

Iz Leakage Reactance (%) of Transformer
Vrms Voltage rating (rms) of transformer
kVA Transformer size

Leakage Inductance

of Transformer (uH)

=

2.65 x Iz x Vrms x Vrms

kVA

Leakage Inductance

of Transformer (uH)

=

3.18 x Iz x Vrms x Vrms

kVA

165 uH

Li ne I nduct ance

Catalog No.

Phase

Hz

kVA

Vrms

%Iz

TMR001-1

3

60

1000

460

5

Leakage Inductance

of Transformer

=

2.65 x 0.05 x 460 x 460

1000

=

28uH