Connecting the ac input, Isolation transformer, Mov protection – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 188: Feeder bay

Publication 2364P-5.01 December 1999
Installation
Connecting the AC Input
Isolation Transformer
The parallel configuration should be supplied with a balanced
3-phase input providing the nominal AC line voltage (plus or minus
the tolerance). To ensure that the AC input is balanced and isolated,
an isolation transformer is recommended.
MOV Protection
The units in the parallel configuration are supplied with MOVs to
handle voltage surges, high phase-to-phase voltages, and high phase-
to-ground voltages. Connecting an input voltage greater than the
listed input voltage tolerance may cause the MOVs to be damaged,
resulting in a continuous current path to ground.
Feeder Bay
The feeder bay allows top or bottom entry, and allows up to 10
connections to be attached for each phase (on alternate sides of the
busbars, if desired). The recommended torque is 45 lb-ft.
Figure 15.14
AC Input Connections
U p to 10 con nections
availab le per ph as e
½ " Holes
Cu stom er S u pp lied A C
In pu t Lines
Recommended Torque
45 lb-ft.