Chapter 5, R4 and s4-code parallel configurations, R4-code parallel configuration – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 55: S4-code parallel configuration, Chapter

Publication 2364P-5.01 December 1999
Chapter
5
R4 and S4-Code Parallel Configurations
R4-Code Parallel Configuration
The R4-code parallel configuration is a common DC bus front-end
unit consisting of an D-code NRU in parallel with an N-code RGU.
Figure 5.1
R4-Code Parallel Configuration–Information
S4-Code Parallel Configuration
The S4-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with an N-code RGU.
Figure 5.2
S4-Code Parallel Configuration–Information
Note: Information for the D-code NRU and E-code NRU can be
found in publication 2364E-5.01. Information for the N-code
RGU can be found in publication 2364F-5.01.
380
1600
821
460
1600
994
575
1591
1235
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
R4-code Parallel Configuration
R4-code Ratings
N-code
RGU
D-code
NRU
380
2100
1077
460
2100
1304
575
2091
1623
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
S4-code Parallel Configuration
S4-code Ratings
N-code
RGU
E-code
NRU