Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual

Page 180

Advertising
background image

Publication 2364P-5.01 December 1999

15-8

Installation

The phase unbalance and undervoltage thresholds are set by the
jumper configuration across terminals 6 through 10. The following
illustration shows how to jumper the relay for different threshold
settings.

Figure 15.6
Jumpers Settings for Phase Imbalance and Undervoltage Thresholds

The typical factory setting, for example, has terminals 6, 8, and 10
jumpered together.

Undervoltage

Terminal Numbers

Threshold

6

7

8

9

10

10.0%

14.0%

17.0%*

20.0%

* Typical factory setting is 17.0%.

Phase Unbalance

Terminal Numbers

Threshold

6

7

8

9

10

5.0%

6.5%

8.0%*

10.0%

* Typical factory setting is 8.0%.