Rgu-to-rgu (r2r) communications – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual

Page 181

Advertising
background image

Publication 2364P-5.01 December 1999

Installation

15-9

RGU-to-RGU (R2R) Communications

If more than one RGU is in the parallel configuration, an
RGU-to-RGU (R2R) communications link will be used to transmit
current commands and status information from the master unit to the
slave unit(s). The fiber optic cables for R2R communications will be
coiled in the slave RGUs.

When working with the fiber optic cables, please note the precautions
in Figure 15.7.

Figure 15.7
Wiring Guidelines

Figures 15.8 and 15.9 show the routing path and connection scheme
that should be used when connecting the R2R fiber optic cables.

Figure 15.8
R2R Fiber Optic Cables–Routing Paths

3 inch (76 mm)

diameter or greater

Radius 1 inch (254 mm)

or greater

Bending Radius

Coiling Excess Cable

Tie Wrap

Do not overtighten tie wraps

The fiber cable should be
able to move freely within
the cable tie wrap.

Routing Path - Master With One Slave

Routing Path - Master With Two Slaves

Hub Board

Wireway