Publication 2364P-5.01 December 1999

1-10

Theory of Operation

If there are two RGUs in the configuration, each RGU will supply up
to 10% of its rated motoring current. If the load is in this 10%, the
RGUs will regulate the bus voltage. The master RGU will evaluate
the bus voltage, and will determine the current required to maintain
the nominal bus voltage (1.52 times the line voltage). The master
RGU will send a current command to the slave RGU, and both RGUs
will begin switching their IGBTs to provide the proper motoring or
regenerative current.

Figure 1.16
NRU With Two RGUs–Motoring

Figure 1.17
NRU With Two RGUs–Regenerating

NRU

3-Phase

AC Line

1.52 x AC Line

Voltage

RGU

RGU

RGU-to-RGU

Communications

Current

(Up to 10% of
the RGU rated

amperes)

Current

(Up to 10% of

RGU rated

amperes)

No

Current

v

V

Motoring - Up to 10% of RGU Rated Amperes

NRU

3-Phase

AC Line

1.35 x AC Line

Voltage

RGU

RGU

RGU-to-RGU

Communications

Current

(10% of the

RGU rated

amperes)

v

V

Motoring - Over 10% of RGU Rated Amperes

Current
(10% of

RGU rated

amperes)

Current

(Up to 100% of

the NRU rated

amperes)

NRU

3-Phase

AC Line

1.52 x AC Line

Voltage

RGU

RGU

RGU-to-RGU

Communications

Current

(Up to 100% of

the RGU rated

amperes)

Current

(Up to 100%
of RGU rated

amperes)

No

Current

v

V