Chapter 3, R2 and s2-code parallel configurations, R2-code parallel configuration – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 35: S2-code parallel configuration, Chapter

Publication 2364P-5.01 December 1999
Chapter
3
R2 and S2-Code Parallel Configurations
R2-Code Parallel Configuration
The R2-code parallel configuration is a common DC bus front-end
unit consisting of an D-code NRU in parallel with a L-code RGU.
Figure 3.1
R2-Code Parallel Configuration–Information
S2-Code Parallel Configuration
The S2-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with a L-code RGU.
Figure 3.2
S2-Code Parallel Configuration–Information
Note: Information for the D-code NRU and E-code NRU can be
found in publication 2364E-5.01. Information for the L-code
RGU can be found in publication 2364F-5.01.
380
1536
788
460
1536
954
575
1533
1190
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
R2-code Parallel Configuration
R2-code Ratings
L-code
RGU
D-code
NRU
380
2036
1045
460
2036
1265
575
2033
1578
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
S2-code Parallel Configuration
S2-code Ratings
L-code
RGU
E-code
NRU