Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual

Page 77

Advertising
background image

Publication 2364P-5.01 December 1999

T2 and V2-Code Parallel Configurations

7-3

Figure 7.4
Overhead Bus Assembly

Feeder

Splice Kit

30" Overhead
Bus Assembly

Flex Bus

Drop Tabs

4" Bus Tabs

To NRU circuit breaker

The RGU AC line is connected to the
bus stubs on the NRU circuit breaker

To Feeder Buswork

End Cap

New and Revised NRU and RGU Components in the T2 and V2 Configurations

NRU

CB1

(T1 config) 2500A, SPB-frame with motor operator

Control power filter, 2kHz

Fuse, NRU CB1 motor operator, 10A, KLDR

Primary fuse for 5kVA control transformer

25A, KLDR (for 380V AC input)

20A, KLDR (for 460V AC input)

17.5A, KLDR (for 575V AC input)

Control power transformer, 5kVA
Control terminal block, 30A, 600V

EA10

F25

F4, F6

PT1
TB10

Overhead bus assembly

RGU

F21, F22

DC bus fuses, 500A, 700V, 170M

F4, F6

PT1
TR1

Primary fuse for 5kVA transformer

25A, KLDR (for 380V AC input)

20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)

Control power transformer, 5kVA
Timer relay (3NO/1NC)

Primary fuse for 10kVA control transformer (Opt 6P)

35A, KLDR (for 380V AC input)

30A, KLDR (for 460V AC input)

25A, KLDR (for 575V AC input)

Control power transformer, 10kVA (Opt 6P)

TB4

Control Terminal block, 30A, 600V

Precharge Lockout Relay (2NO/2NC)

CR4

(V1 config) 3000A, SPB-frame with motor operator

Advertising