Chapter 9, T4 and v4-code parallel configurations, T4-code parallel configuration – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 95: V4-code parallel configuration, Chapter

Publication 2364P-5.01 December 1999
Chapter
9
T4 and V4-Code Parallel Configurations
T4-Code Parallel Configuration
The T4-code parallel configuration is a common DC bus front-end
unit consisting of an F-code NRU in parallel with a N-code RGU.
Figure 9.1
T4-Code Parallel Configuration–Information
V4-Code Parallel Configuration
The V4-code parallel configuration is a common DC bus front-end
unit consisting of an G-code NRU in parallel with a N-code RGU.
Figure 9.2
V4-Code Parallel Configuration–Information
Note: Information for the F-code NRU and G-code NRU can be
found in publication 2364E-5.01. Information for the N-code
RGU can be found in publication 2364F-5.01.
380
2600
1334
460
2600
1615
575
2591
2012
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
T4-code Parallel Configuration
T4-code Ratings
N-code
RGU
F-code
NRU
380
3000
1539
460
3000
1863
575
3000
2329
Input Voltage
(V AC)
DC Bus Current
(A DC)
Rated DC Bus
kW
V4-code Parallel Configuration
V4-code Ratings
N-code
RGU
G-code
NRU