Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual

Page 16

Advertising
background image

Publication 1794-UM062A-EN-P - September 2012

8

Install Your FLEX I/O Module

Methods of wiring the terminal base units are shown in the illustration below.

Digital Input

Module

Analog

Module

Analog

Module

Analog

Module

Digital Output

Module

Digital Input

Module

TC/RTD/mV

Module

Analog

Module

TC/RTD/mV

Module

TC/RTD/mV

Module

TC/RTD/mV

Module

TC/RTD/mV

Module

Daisychain

Individual

Combination

24V DC

24V DC

24V DC

24V DC

24V DC

24V DC

45318

Wiring when total current draw is less than 10A

Wiring when total current draw is less than 10A

Total current draw through any base unit must not be greater than 10A

ATTENTION: Note the following rules for each type of wiring
configuration:

• Daisychain – AIl modules must be analog or TC/RTD/mV modules

for this configuration.

• Individual – Use this type of configuration for any noisy DC digital

I/O modules in your system.

• Combination – All modules powered by the same power supply

must be analog modules for the combination type of
configuration.