Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual

Page 52

Advertising
background image

Publication 1794-UM062A-EN-P - September 2012

44

Data Tables

1794-IE8 Series B and 1794-IE8XT – 8 Input Analog Module Image Table Mapping

Memory Map – 1794-IE8/B and 1794-IE8XT Analog Input Module

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

S

Analog Value Channel 0

Read Word 0

S

Analog Value Channel 1

Read Word 1

S

Analog Value Channel 2

Read Word 2

S

Analog Value Channel 3

Read Word 3

S

Analog Value Channel 4

Read Word 4

S

Analog Value Channel 5

Read Word 5

S

Analog Value Channel 6

Read Word 6

S

Analog Value Channel 7

Read Word 7

PU

Not used – set to zero

U7

U6

U5

U4

U3

U2

U1

U0

Read Word 8

C7

C6

C5

C4

C3

C2

C1

C0

F7

F6

F5

F4

F3

F2

F1

F0

Write Word 0

Not used

Write Word 1…5

Where:

PU = Power up bit – included in series B modules only.
U = Underrange bits for 4…20 mA inputs
C = Configure select bit
F = Full range bit
S = sign bit (in 2’s complement)

Module Image

I/O Image

Input Data Channel 0

Input Data Channel 1

Input Data Channel 2

Input Data Channel 3

Input Data Channel 4

Input Data Channel 5

Input Data Channel 6

Input Data Channel 7

Underrange

Configure select

Not used

Not used

Not used

Not used

Not used

Input Size

Output Size

0 or 1 W o r d

1 to 9 W ords

PU

46064

Advertising