Data Tables 63

Word/Bit Descriptions – 1794-IE8XOE4 Analog Combo Module

Word

Decimal Bit
(Octal Bit)

Definition

Read Word 0

Bits 00…14
(00…16)

Channel 0 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 0 analog data sign bit.

Read word 1

Bits 00…14
(00…16)

Channel 1 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 1 analog data sign bit.

Read word 2

Bits 00…14
(00…16)

Channel 2 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 2 analog data sign bit.

Read word 3

Bits 00…14
(00…16)

Channel 3 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 3 analog data sign bit.

Read word 4

Bits 00…14
(00…16)

Channel 4 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 4 analog data sign bit.

Read word 5

Bits 00…14
(00…16)

Channel 5 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 5 analog data sign bit.

Read word 6

Bits 00…14
(00…16)

Channel 6 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 6 analog data sign bit.

Read word 7

Bits 00…14
(00…16)

Channel 7 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 7 analog data sign bit.