Data Tables

S

Analog Data – Output Channel 3

Write word 4

QS

0

0

0

CAB

C89

C67

C45

C23

C01

Write word 5

Where:

PU = Power up bit
FP = Field power fault
GF = General fault
NU = Not used
Wx = Wire off (x = associated channel)
Rx = Out of range (x = associated channel)
EN = Enable outputs
S1/S0 = Safe state source - When EN = 0, these bits indicate source of safe state output.
WR = Wire-off reset
QS = Quick step bit - allows input filter to be reduced during rapid signal changes.
Cxx = Channel Configuration (xx = associated channel pair)

Memory Map – 1794-IE8XOE4 Analog Combo Module

Decimal Bit 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

Range Selection Bits – 1794-IE8XOE4 Analog Combo Module

Range

Out of Range

Range Setting

Cxx Channel
Configuration

-10…+10V DC

1< -10.0V or > 10.0V

Set bits for each
channel pair
00 = off
01 = 0…20 mA
10 = 4…20 mA
11 = ±10V

C01 for channels 0 and 1
C23 for channels 2 and 3
C45 for channels 4 and 5
C67 for channels 6 and 7
C89 for channels 8 and 9
CAB for channels 10 and 11

4…20 mA

<4.0 mA or >20.0 mA

0…20 mA

<0.0 mA or >20.0 mA

Where:

Cxx = associated channel pair.

Safe State Selection Bits – 1794-IE8XOE4 Analog Combo Module

S1/S0 Safe State
Select Source

Safe State Mode

Safe State Output Behavior

S1

S0

0

0

Safe State value is in the
output words

Outputs use Safe State value

0

1

Reserved (Safe State value
is in the output words)

Reserved (Outputs use Safe State
value)

1

0

Clear/Reset the outputs,
based on range selected

+10V range – Output set to 0V
4…20 mA range – Output set to 4 mA
0…20 mA range – Output set to 0 mA

1

1

Hold output at its present
level

Outputs Hold Last State