Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual

Page 30

Advertising
background image

Publication 1794-UM062A-EN-P - September 2012

22

Install Your FLEX I/O Module

Output 10

Current

I

B-27

C-46

Voltage

V

B-28

Output 11

Current

I

B-29

C-48

Voltage

V

B-30

24V DC common

1794-TB3G – C-35, C-51

(1)

1794-TB3GS – C-35, C-51

+24V DC power

1794-TB3G – C-34, C-50

(2)

1794-TB3GS – C-34, C-50

Chassis ground
(Shield)

1794-TB3G – B-16, B-33, C-38, C-40…45, C-47

(3)

1794-TB3GS – B-16, B-33, C-38, C-40…45, C-47

(1)

Terminals C-35 and C-51 are internally connected in the terminal base unit.

(2)

Terminals C-34 and C-50 are internally connected in the terminal base unit.

(3)

Terminals B-16, B-33, C-38, C-40 through C- 45, and C-47 are internally connected to chassis ground

Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE8XOE4 Module

Channel

Signal Type

Label
Marking

1794-TB3G or 1794-TB3GS

Input/Output

Common Terminal

Input 0

Current

I0

A-0

B-17

Voltage

V0

A-1

Input 1

Current

I1

A-2

B-18

Voltage

V1

A-3

Input 2

Current

I2

A-4

B-23

Voltage

V2

A-5

Input 3

Current

I3

A-6

B-24

Voltage

V3

A-7

Input 4

Current

I4

A-8

B-25

Voltage

V4

A-9

Input 5

Current

I5

A-10

B-26

Voltage

V5

A-11

Input 6

Current

I6

A-12

B-31

Voltage

V6

A-13

Input 7

Current

I7

A-14

B-32

Voltage

V7

A-15

Wire Connections for 1794-TB3G, and 1794-TB3GS using the 1794-OE12 Module

Channel

Signal Type

Label
Markings

1794-TB3G and 1794-TB3GS

Output

Common Terminal

Advertising