Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual

Page 27

Advertising
background image

Publication 1794-UM062A-EN-P - September 2012

Install Your FLEX I/O Module 19

Connect Wiring Using a 1794-TB3G or 1794-TB3GS Terminal
Base Unit

1. Connect individual signal wiring to numbered terminals on 0…15 row

(A), and 17…32 row (B) for 1794-TB3G and 1794-TB3GS as indicated in
the following tables.

2. Connect any signal wiring shields to functional ground as near as possible

to the module.
1794-TB3G and 1794-TB3GS only: Connect to earth ground terminals
B16, B33, C38, C40…C45 and C47.

3. Connect the -V DC common (return) to terminal 35 on the 34…51

row (C).

Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE4XOE2 Module

Channel

Signal Type

Label
Markings

1794-TB2 and 1794-TB3

Signal

Common Terminal

Input 0

Current

I

0

17

Voltage

V

1

18

Input 1

Current

I

2

19

Voltage

V

3

20

Input 2

Current

I

4

21

Voltage

V

5

22

Input 3

Current

I

6

23

Voltage

V

7

24

Output 0

Current signal

I

8

Current common

RET

9

(2)

Voltage signal

V

10

Voltage common

RET

11

(2)

Output 1

Current signal

I

12

Current common

V

13

(2)

Voltage signal

I

14

Voltage common

V

15

(2)

24V DC Common

16…33

(1)

+24V DC Power

1794-TB2 – 34…51
1794-TB3 – 34…51

(1)

Terminals 16…33 are internally connected in the terminal base unit.

(2)

Terminals 9, 11, 13, and 15 are internally connected in the module to 24V DC common.