Install Your FLEX I/O Module 17

the 24V DC common/return from terminal 33 on this base unit to terminal 16
on the next base unit.

Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE8 Module

Channel

Signal Type

Label
Markings

1794-TB2 and 1794-TB3

Input

Common Terminal

Input 0

Current

I

A-0

B-17

Voltage

V

A-1

B-18

Input 1

Current

I

A-2

B-19

Voltage

V

A-3

B-20

Input 2

Current

I

A-4

B-21

Voltage

V

A-5

B-22

Input 3

Current

I

A-6

B-23

Voltage

V

A-7

B-24

Input 4

Current

I

A-8

B-25

Voltage

V

A-9

B-26

Input 5

Current

I

A-10

B-27

Voltage

V

A-11

B-28

Input 6

Current

I

A-12

B-29

Voltage

V

A-13

B-30

Input 7

Current

I

A-14

B-31

Voltage

V

A-15

B-32

24V DC common

B-16…33

(1)

(1)

Terminals 16…33 are internally connected in the terminal base unit.

+24V DC power

1794-TB2 – C-34…51
1794-TB3 – C-34…51

Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-OE8 Module

Channel

Signal Type

Label
Markings

1794-TB2 and 1794-TB3

Output

Output 1

Current signal

I

A-0

Current common

RET

A-1

(1)

Voltage signal

V

A-2

Voltage common

RET

A-3

(1)

Current signal

I

A-4

Current common

RET

A-5

(1)

Voltage signal

V

A-6

Voltage common

RET

A-7

(1)