Publication 1794-UM062A-EN-P - September 2012

58

Data Tables

Memory Map – 1794-IE4XOE2/B and 1794-IE4XOE2XT Analog Combo Module

Decimal Bit 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

S

Analog Value Channel 0

Read word 1

S

Analog Value Channel 1

Read word 2

S

Analog Value Channel 2

Read word 3

S

Analog Value Channel 3

Read word 4

PU

Not used – set to 0

W1 W0 U3

U2

U1

U0

Read word 5

S

Analog Data – Output Channel 0

Write word 1

S

Analog Data – Output Channel 1

Write word 2

Not used – set to 0

OE1 OE0

Write word 3

Not used

C5

C4

C3

C2

C1

C0

0

0

F5

F4

F3

F2

F1

F0

Write word 4

Not used – set to 0

Write word 5…10

Where:

PU = Power up bit – included in series B modules only.
W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.)
U = Underrange bits for 4…20 mA inputs
S = Sign bit (in 2’s complement)
OE = Output enable bits (bit 00 corresponds to output 0, bit 01 corresponds to output 1, and so on.
C = Configure select bit
F = Full range bit

Module Image

I/O Image

Input Data Channel 0

Input Data Channel 1

Input Data Channel 2

Input Data Channel 3

Output Data Channel 0

Output Data Channel 1

Underrange & Diag.

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Full Range and Configure Select

Not used

Input Size

Output Size

0 to 4 Words

0 to 5 Words

Read

Write

OE

PU