Publication 1794-UM062A-EN-P - September 2012

32

Communicate With Your Module

Polled I/O Structure

Output data is received by the adapter in the order of the installed I/O modules.
The Output data for Slot 0 is received first, followed by the Output data for Slot
1, and so on up to slot 7.

The first word of input data sent by the adapter is the Adapter Status Word. This
is followed by the input data from each slot, in the order of installed I/O
modules. The Input data from Slot 0 is first after the status word, followed by
Input data from Slot 2, and so on to slot 7.

Adapter Input Status Word

The input status word consists of:

• I/O module fault bits — 1 status bit for each slot
• node address changed — 1 bit
• I/O status — 1 bit

Adapter status

Slot 0 input data

Slot 1 input data

Slot 7 input data

Slot 0 output data

Slot 1 output data

Slot 7 output data

Read data

Write data

Network READ

Network WRITE

FLEX I/O adapter

slot 0

I/O module

Read

Write

slot 1

I/O module

slot 7

I/O module

...

...

...

...

...

46062

15

Bit:

0

1

2

3

4

5

6

7

8

10 through 15

I/O Module Fault Bits

Node Address Changed Bit

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

9

I/O State Bit

Not Used

46063