Publication 1794-UM062A-EN-P - September 2012

16

Install Your FLEX I/O Module

Connect Wiring to the FLEX
I/O Module

Wiring to the analog module is made through the terminal base unit on which
the module mounts.

Verify which terminal base units your module is compatible with in table

Module

and Terminal Base Unit Compatibility on page 16

.

Connect Wiring Using a 1794-TB2 or 1794-TB3 Terminal Base Unit

1. Connect the individual signal wiring to numbered terminals on the 0…15

row (A) on the terminal base unit. Use Belden 8761 cable for signal wiring.

2. Connect each channel signal return to:

• 1794-IE8 – the associated terminal on row (B).
• 1794-OE4 – the corresponding terminal on the same row (A).
• 1794-IE4XOE2 – inputs: the associated terminal on row (B); outputs:

the corresponding terminal on the same row (A).

3. Connect +24V DC to designated terminals on the 34…51 row (C), and

24V common to designated terminals on the 16…33 row (B).

If daisy chaining the +24V DC power to the next base unit, connect a jumper
from terminal 51 on this base unit to terminal 34 on the next base unit. Connect

Module and Terminal Base Unit Compatibility

Module

1794-TB2 1794-TB3 1794-TB3S 1794-TB3G 1794-TB3GS 1794-TB3T

1794-TB3TS

TBN

1794-IE8

Yes

Yes

No

No

No

No

No

No

1794-IE8XT

Yes

Yes

Yes

No

No

Yes

Yes

No

1794-IE12

No

No

No

Yes

Yes

No

No

No

1794-OE12

No

No

No

Yes

Yes

No

No

No

1794-OE4

Yes

Yes

No

No

No

No

No

No

1794-OE4XT

Yes

Yes

Yes

No

No

Yes

Yes

Yes

1794-IE4XOE2

Yes

Yes

No

No

No

No

No

No

1794-IE4XOE2XT

Yes

Yes

Yes

No

No

Yes

Yes

No

1794-IE8XOE4

No

No

No

Yes

Yes

No

No

No

ATTENTION: Connect only one current or one voltage signal per
channel. Do not connect both current and voltage on one channel.

ATTENTION: To reduce susceptibility to noise, power analog
modules and discrete modules from separate power supplies. Do
not exceed a length of 10 m (33 ft) for power cabling.