Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual

Page 59

Advertising
background image

Publication 1794-UM062A-EN-P - September 2012

Data Tables 51

1794-OE4 Series B and 1794-OE4XT– 4 Output Analog Module Image Table Mapping

Memory Map – 1794-OE4/B and 1794-OE4XT Analog Output Module

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

PU

Not used – set to 0

W3

W2

W1

W0

Read word 0

S

Analog Value Channel 0

Write word 0

S

Analog Value Channel 1

Write word 1

S

Analog Value Channel 2

Write word 2

S

Analog Value Channel 3

Write word 3

Not used – set to 0

M3

M2

M1

M0

Write word 4

Not used – set to 0

C3

C2

C1

C0

Not used – set to 0

F3

F2

F1

F0

Write word 5

Not used – set to 0

Write words 6…9

S

Safe State Value – Channel 0

Write word 10

S

Safe State Value – Channel 1

Write word 11

S

Safe State Value – Channel 2

Write word 12

S

Safe State Value – Channel 3

Write word 13

Where:

PU = Power up bit
W = Diagnostic bits for current output wire broken or load resistance high. Not used on voltage outputs.
S = Sign bit (in 2’s complement)
M = Multiplex control
C = Configure select bit
F = Full range bit