Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual
Page 59

Publication 1794-UM062A-EN-P - September 2012
Data Tables 51
1794-OE4 Series B and 1794-OE4XT– 4 Output Analog Module Image Table Mapping
Memory Map – 1794-OE4/B and 1794-OE4XT Analog Output Module
Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read/Write Words
PU
Not used – set to 0
W3
W2
W1
W0
Read word 0
S
Analog Value Channel 0
Write word 0
S
Analog Value Channel 1
Write word 1
S
Analog Value Channel 2
Write word 2
S
Analog Value Channel 3
Write word 3
Not used – set to 0
M3
M2
M1
M0
Write word 4
Not used – set to 0
C3
C2
C1
C0
Not used – set to 0
F3
F2
F1
F0
Write word 5
Not used – set to 0
Write words 6…9
S
Safe State Value – Channel 0
Write word 10
S
Safe State Value – Channel 1
Write word 11
S
Safe State Value – Channel 2
Write word 12
S
Safe State Value – Channel 3
Write word 13
Where:
PU = Power up bit
W = Diagnostic bits for current output wire broken or load resistance high. Not used on voltage outputs.
S = Sign bit (in 2’s complement)
M = Multiplex control
C = Configure select bit
F = Full range bit